Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/06/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* OK TO CLEAR ECO. RAY MIGHT HAVE ALREADY SENT CLEARANCE? |
| 04/25/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* INSTALL REJECTION PINS IN SERVICE DISCONNECT |
| 05/14/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
1) ID ALL DISCONNECTS INCLUDING MAIN PERMANENETLY. 2) INSTALL REJECT PINS ALL DISCONNECTS. 3) STRAP ALL FLEX FEEDERS. 4) CHASE OUT PROBLEM IN 400A DISCON OR RUN NEW FEEDERS. 5) CLOSE ALL UNUSED OPENINGS. SINCE EXISTING MAIN DOES NOT HAVE A NUETRAL NEW GROUND MOUNTED IN GUTTER TO ALL GROUNDS . NOTE: EE APPROVED PLAN SHOW USE EXISTING 1200 A MAIN DISCONNECT. CALL FOR FINAL OR FOR APPROVAL PRIOR TO ENERGIZE 400A DISCONNECT. CONTRACTOR PAID FOR INSP. |
| 05/13/2004 |
ELECTRIC - FINAL |
|
Partial Approval |
SWITCH GEAR TO COMPLEX SHORTED OUT-BUSS MELTED, GEAR DESTROYED AT MAIN SECTION. AN ENGINEERED PLAN APPROVED THROUGH PLAN FOR REPAIR OR REPLACEMENT WILL BE REQUIRED PRIOR TO ANY INSPECTIONS, PERMIT REQUIRED. POWER WAS DISCONNECTED AT POLE CUT OUTS BY TEP COMPLEX WITHOUT POWER, 1200 AMP 480 VOLT 3 DIAMETER. NO STRUCTUAL DAMAGE PER ART MATHIESON ON 5/14/04 |