Permit: T04EL00884
Permit Details
Apply Date:
04/30/2004
Applicant:
PUEBLO ELECTRIC SERVICES *C
Description:
UPGRADE: 200 AMP (APA)
Contractors:
- PUEBLO ELECTRIC SERVICES *C
Outstanding Activity Conditions
Permit Number - T04EL00884
Permit Status: Final
Permit Description: UPGRADE: 200 AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/30/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04EL00884
Permit Description: UPGRADE: 200 AMP (APA)
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2004 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PERMANENT METAL ADDRESS LABEL IS NEEDED 2) SEALING DEVICES NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 3) USE APPROVED FITTINGS WITH LB. CHASE NIPPLE NOT APPROVED 4) PLEASE PROVIDE CUT PIECES OF GROUND ROD TO VERIFY LENGTH OF ROD-GROUNDING ELECTRODE ELECTRODE TO BE FROM ROD TO ROD 5) SUPPORT PVC CONDUIT ON SIDE OF PANEL 6) GROUNDING EQUIPMENT CONDUCTOR TO TERMINATE INTO LUGS NOT SPLICED WITH WIRE NUT 7) NEUTRAL COJNDUCTOR TO BE WHITE ENTIRE LENGTH 200.7 8) RISER HARDWARE TO BE 1/4" MINIMUM 9) DRY WALL SCREWS NOT ALLOWED AS MOUNTING HARDWARE |
| 01/25/2005 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection :* |
| 01/25/2005 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection :* |
| 01/26/2005 | PERMIT FINALED | JKOZUCH | Approved | |
| 01/26/2005 | TEP CLEARANCE - AM | SLONG | Approved | INC |