Permit: T04EL00884

Parcel: 121011260


Addresses:

6018 E SENECA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/25/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*OK TO CLEAR INCREASE
01/19/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/03/2004 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) PERMANENT METAL ADDRESS LABEL IS NEEDED 2) SEALING DEVICES NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 3) USE APPROVED FITTINGS WITH LB. CHASE NIPPLE NOT APPROVED 4) PLEASE PROVIDE CUT PIECES OF GROUND ROD TO VERIFY LENGTH OF ROD-GROUNDING ELECTRODE ELECTRODE TO BE FROM ROD TO ROD 5) SUPPORT PVC CONDUIT ON SIDE OF PANEL 6) GROUNDING EQUIPMENT CONDUCTOR TO TERMINATE INTO LUGS NOT SPLICED WITH WIRE NUT 7) NEUTRAL COJNDUCTOR TO BE WHITE ENTIRE LENGTH 200.7 8) RISER HARDWARE TO BE 1/4" MINIMUM 9) DRY WALL SCREWS NOT ALLOWED AS MOUNTING HARDWARE