Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK TO CLEAR INCREASE | |
| 01/19/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/03/2004 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) PERMANENT METAL ADDRESS LABEL IS NEEDED 2) SEALING DEVICES NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS 3) USE APPROVED FITTINGS WITH LB. CHASE NIPPLE NOT APPROVED 4) PLEASE PROVIDE CUT PIECES OF GROUND ROD TO VERIFY LENGTH OF ROD-GROUNDING ELECTRODE ELECTRODE TO BE FROM ROD TO ROD 5) SUPPORT PVC CONDUIT ON SIDE OF PANEL 6) GROUNDING EQUIPMENT CONDUCTOR TO TERMINATE INTO LUGS NOT SPLICED WITH WIRE NUT 7) NEUTRAL COJNDUCTOR TO BE WHITE ENTIRE LENGTH 200.7 8) RISER HARDWARE TO BE 1/4" MINIMUM 9) DRY WALL SCREWS NOT ALLOWED AS MOUNTING HARDWARE |