Permit: T04EL00526
Permit Details
Apply Date:
03/15/2004
Applicant:
BERNADETTE CRUZ
Description:
ELECTRIC:RECONNECT
Outstanding Activity Conditions
Permit Number - T04EL00526
Permit Status: Expired
Permit Description: ELECTRIC:RECONNECT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/15/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL00526
Permite Description: ELECTRIC:RECONNECT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2004 | ELECTRIC - RECONNECT | N/A | Denied | IVRS - Inspection 0999*/ 1) SERVICE PANEL REQUIRES PERMANENT ADDRESS 2) SERVICE REQUIRES NEW GROUNDING SYSTEM (2 GRD RODS, GAS AND WATER BOND ) 3) RISER TO BE RIGID SUPPORTED 4) NICKED #12 HOT WIRE IN SERVICE ENCLOSURE 5) IMPROPER FITTING USED TO CONNECT LB FITTING AND SERVICE ENCLOSURE 6) NEED A RECEPTACLE OUTSIDE BY COOLER FOR COOLER 7) CORRECT AND RECALL |
| 03/29/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999*/ TERMINATIONS AT 30A DISCONNECT ARE CRYSTALLIZING. SWITCH DOES NOT WORK WELL, IS IN POOR CONDITION - IT'S TIME TO CHANGE OUT AND BE BROUGHT TO CURRENT CODE. OUTSIDE WTR HTR TO BE ENCLOSED. OUTSIDE COOLER WIRING EXIST IN A HAZARDOUS MANNER #1 ITEM ABOVE NEEDS CORRECTION. |