Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2004 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*/ 1) SERVICE PANEL REQUIRES PERMANENT ADDRESS 2) SERVICE REQUIRES NEW GROUNDING SYSTEM (2 GRD RODS, GAS AND WATER BOND ) 3) RISER TO BE RIGID SUPPORTED 4) NICKED #12 HOT WIRE IN SERVICE ENCLOSURE 5) IMPROPER FITTING USED TO CONNECT LB FITTING AND SERVICE ENCLOSURE 6) NEED A RECEPTACLE OUTSIDE BY COOLER FOR COOLER 7) CORRECT AND RECALL |
| 03/16/2004 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*/ 1) GROUNDED RECEPTACLES ON AN UN-GROUNDED SYSTEM 2) A RECEPTACLE IS NEEDED FOR KITCHEN 3) PROPERLY AND SAFELY HOOK-UP COOLER 4) SERVICE IS AN OLD 110V SERVICE IN A DETERIORATED CONDITION. DISCONNECT IS RUSTED OUT-CONDUCTORS BRITTLE AND DRY 5) A LICENSE ELECTRICAL CONTRACTOR TO PERFORM WORK |