Permit: T04EL00503
Permit Details
Apply Date:
03/11/2004
Applicant:
DONNELLY ELIZABETH K & DONNELLY
Description:
UPGRADE: TO 200 AMP PLUS NEW PEDASTAL
Permit Reviews
Permit Number - T04EL00503
Permit Status: Expired
Permit Description: UPGRADE: TO 200 AMP PLUS NEW PEDASTAL
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/11/2004 | ELECTRICAL | 03/11/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL00503
Permit Status: Expired
Permit Description: UPGRADE: TO 200 AMP PLUS NEW PEDASTAL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/11/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL00503
Permite Description: UPGRADE: TO 200 AMP PLUS NEW PEDASTAL
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/12/2004 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0999* |
| 03/12/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999*/ 1) APPROVED FITTINGS NEEDED FOR 2B. EMT CONNECTOR OR CHASE NIPPLE NOT APPROVED. 2) TIGHTEN LOOSE FITTINGS. 3) SUPPORT CONDUIT. 4) CANNOT LOCATE GROUND RODS, GAS OR WTR BOND. 5) GROUNDING EQUIPMENT CONDUCTOR FOR A/C NOT SIZED CORRECTLY. 6) PLEASE VERIFY PERMIT FOR NEW A/C 7) WHERE IS PEDISTAL? |