Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/12/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) APPROVED FITTINGS NEEDED FOR 2B. EMT CONNECTOR OR CHASE NIPPLE NOT APPROVED. 2) TIGHTEN LOOSE FITTINGS. 3) SUPPORT CONDUIT. 4) CANNOT LOCATE GROUND RODS, GAS OR WTR BOND. 5) GROUNDING EQUIPMENT CONDUCTOR FOR A/C NOT SIZED CORRECTLY. 6) PLEASE VERIFY PERMIT FOR NEW A/C 7) WHERE IS PEDISTAL? |