Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04EL00108
Permit Details
Apply Date:
01/16/2004
Applicant:
MARISCAL ESTHER
Description:
RECONNECT:ELECTRIC OFFICE
Outstanding Activity Conditions
Permit Number - T04EL00108
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC OFFICE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/16/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL00108
Permite Description: RECONNECT:ELECTRIC OFFICE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* N.M. CABLE NEEDS CONNECTORS WHERE ENTERING J-BOXES. ALL METAL J-BOXES NEED TO BE PROPERLY GROUNDED PER N.E.C. SEAL ALL UNUSED OPENINGS IN J-BOXES REMOVE DOUBLE LUGGING AT 100 AMP DISCONNECT SWITCH. SEAL UNUSED OPENINGS AT SERVICE EQUIP. REMOVE DELAMINATED PLYWOOD BEHIND SERVICE EQUIP. ELECTRIC SERVICE NEEDS TO BE UPGRADED. EQUIP IS OLD & DILAPIDATED GETTER, DISCONNECT CLIPS ETC. |
Completed Inspections
Permit Status: Expired
Permit Number: T04EL00108
Permit Description: RECONNECT:ELECTRIC OFFICE
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2004 | FIRE - FINAL | LTHOMAS | Approved | Fire approval for electric reconnect only. |