Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address NEW:
4842 E SPEEDWAY BL
Apply Date:
01/16/2004
Applicant:
MARISCAL ESTHER
Description:
RECONNECT:ELECTRIC OFFICE

Outstanding Activity Conditions

Permit Number - T04EL00108
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC OFFICE
Total Outstanding Activity Conditions - 1
Date Name
01/16/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04EL00108
Permite Description: RECONNECT:ELECTRIC OFFICE
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
01/20/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection 0999* N.M. CABLE NEEDS CONNECTORS WHERE ENTERING J-BOXES. ALL METAL J-BOXES NEED TO BE PROPERLY GROUNDED PER N.E.C. SEAL ALL UNUSED OPENINGS IN J-BOXES REMOVE DOUBLE LUGGING AT 100 AMP DISCONNECT SWITCH. SEAL UNUSED OPENINGS AT SERVICE EQUIP. REMOVE DELAMINATED PLYWOOD BEHIND SERVICE EQUIP. ELECTRIC SERVICE NEEDS TO BE UPGRADED. EQUIP IS OLD & DILAPIDATED GETTER, DISCONNECT CLIPS ETC.

Completed Inspections

Permit Status: Expired
Permit Number: T04EL00108
Permit Description: RECONNECT:ELECTRIC OFFICE
Total Completed Inspections - 1
Date Description Inspector Results Comments
01/22/2004 FIRE - FINAL LTHOMAS Approved Fire approval for electric reconnect only.

Documents

File Name Document Type  
None DOCUMENTS VIEW