Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/20/2004 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999* N.M. CABLE NEEDS CONNECTORS WHERE ENTERING J-BOXES. ALL METAL J-BOXES NEED TO BE PROPERLY GROUNDED PER N.E.C. SEAL ALL UNUSED OPENINGS IN J-BOXES REMOVE DOUBLE LUGGING AT 100 AMP DISCONNECT SWITCH. SEAL UNUSED OPENINGS AT SERVICE EQUIP. REMOVE DELAMINATED PLYWOOD BEHIND SERVICE EQUIP. ELECTRIC SERVICE NEEDS TO BE UPGRADED. EQUIP IS OLD & DILAPIDATED GETTER, DISCONNECT CLIPS ETC. |