Permit: T04EL00056
Permit Details
Apply Date:
01/09/2004
Applicant:
WEYENBERG RONALD G & MARTA G CP/RS
Description:
UPGRADE:ELECTRIC TO 200 AMP
Outstanding Activity Conditions
Permit Number - T04EL00056
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC TO 200 AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/09/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL00056
Permite Description: UPGRADE:ELECTRIC TO 200 AMP
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2004 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0215* |
| 01/13/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0215*/ CORRECTIONS: 1) A METAL EMBOSSED OR STRAPPED ADDRESS MUST BE PLACED ON THE METER SIDE [ABOVE OR BELOW METER]. THE METAL STRIP MUST BE SECURED TO THE PANEL WITH SCREWS OR RIVITS. 2) WHERE IS THE GAS PIPE AND WTR PIPE GROUND BOND? MUST BE INSPECTED. 3) ADD A STRAP TO THE RISER PIPE WITHIN 8" OF THE PANEL. CORRECT AND RECALL. |