Permit: T04EL00056

Parcel: 125080560


Addresses:

215 N NORTON AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/13/2004 ELECTRIC - FINAL Denied IVRS - Inspection 0215*/ CORRECTIONS: 1) A METAL EMBOSSED OR STRAPPED ADDRESS MUST BE PLACED ON THE METER SIDE [ABOVE OR BELOW METER]. THE METAL STRIP MUST BE SECURED TO THE PANEL WITH SCREWS OR RIVITS. 2) WHERE IS THE GAS PIPE AND WTR PIPE GROUND BOND? MUST BE INSPECTED. 3) ADD A STRAP TO THE RISER PIPE WITHIN 8" OF THE PANEL. CORRECT AND RECALL.