Permit: T04EL00001
Permit Details
Apply Date:
01/02/2004
Applicant:
DUGIE CHRISTOPHER
Description:
ELECTRIC:REPLACE SERVICE
Permit Reviews
Permit Number - T04EL00001
Permit Status: Expired
Permit Description: ELECTRIC:REPLACE SERVICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/02/2004 | ELECTRICAL | 01/02/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04EL00001
Permit Status: Expired
Permit Description: ELECTRIC:REPLACE SERVICE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/02/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04EL00001
Permite Description: ELECTRIC:REPLACE SERVICE
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/18/2004 | ELECTRIC - SERVICE UPGRADE | N/A | Denied | IVRS - Inspection 0999*/ 1) GROUNDING BUSHING AND BOND JUMPER REQUIRED AT BOTH SIDES OF 2" NIPPLE 2) IMPROPER CLEARANCE IN FRONT OF SERVICE (28") MUST HAVE 36" MINIMUM 3) INSTALL A GROUNDING ELECTRODE SYSTEM ALONG WITH WATER BOND AND GAS BOND (IF AVAILABLE) 4) NEED PERMANENT METAL ADDRESS TAG |
| 03/18/2004 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* |