Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 03/18/2004 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*/ 1) GROUNDING BUSHING AND BOND JUMPER REQUIRED AT BOTH SIDES OF 2" NIPPLE 2) IMPROPER CLEARANCE IN FRONT OF SERVICE (28") MUST HAVE 36" MINIMUM 3) INSTALL A GROUNDING ELECTRODE SYSTEM ALONG WITH WATER BOND AND GAS BOND (IF AVAILABLE) 4) NEED PERMANENT METAL ADDRESS TAG |