Permit Details

Status:
Expired
Type:
SINGLE FAMILY ADDITION
Address:
1035 N 11TH AV
Address NEW:
1035 N 11TH AV
Apply Date:
08/03/2004
Applicant:
RYSZARD KUPSINSKI
Description:
ALTERATION: ENCLOSE CARPORT T03ZV00084 T03VL00666 T03SW04420 T03DV00612

Permit Reviews

Permit Number - T04CM03583
Permit Status: Expired
Permit Description: ALTERATION: ENCLOSE CARPORT T03ZV00084 T03VL00666 T03SW04420 T03DV00612
Start Date Submittal Complete Date Status  
08/03/2004 RESIDENTIAL BLDG/ZONING-WALKTHRU 08/11/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM03583
Permit Status: Expired
Permit Description: ALTERATION: ENCLOSE CARPORT T03ZV00084 T03VL00666 T03SW04420 T03DV00612
Total Outstanding Activity Conditions - 1
Date Name
08/03/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T04CM03583
Permite Description: ALTERATION: ENCLOSE CARPORT T03ZV00084 T03VL00666 T03SW04420 T03DV00612
Total Outstanding Inspections - 4
Last Inspection Date Description Inspector Results Comments
11/03/2004 BUILDING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*/ 1) TOILET REQUIRES 15" CLEARANCE FROM CENTER LINE TO SIDE OBSTRUCTION
2) UNDERGROUNDED ELECTRIC OUTLETS NOT ALLOWED
3) ELECTRIC PANEL IS UNDERGROUNDED INSTALL TWO EACH 8 FEET GROUND RODS AT LEAST 6 FEET APART CONNECTED TO SERVICE PANEL WITH A CONTINOUS #4 CONDUCTOR
4) #12 WIRE CANNOT BE ON CIRCUIT BREAKER LARGER THAN 20 AMP. PRESENTLY 40 AMP
5) SHOWER APPEARS TO HAVE NO "P" TRAP. EXPOSE ALL PLUMBING
6) EXPOSE ALL ELECTRICAL
7) MAIN HOUSE BEDROOMS MUST HAVE AT LEAST BATTERY OPERATED SMOKE DETECTORS
8) BATHROOM REQUIRES GFCI CIRCUIT
9) ELECTRIC OUTLETS REQUIRED WITHIN 6 FEET OF DOOR
11/03/2004 ELECTRIC - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/03/2004 PLUMBING - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/03/2004 MECHANICAL - FINAL N/A Denied IVRS - Inspection :
See detailed listing on site.| 999*