Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) TOILET REQUIRES 15" CLEARANCE FROM CENTER LINE TO SIDE OBSTRUCTION 2) UNDERGROUNDED ELECTRIC OUTLETS NOT ALLOWED 3) ELECTRIC PANEL IS UNDERGROUNDED INSTALL TWO EACH 8 FEET GROUND RODS AT LEAST 6 FEET APART CONNECTED TO SERVICE PANEL WITH A CONTINOUS #4 CONDUCTOR 4) #12 WIRE CANNOT BE ON CIRCUIT BREAKER LARGER THAN 20 AMP. PRESENTLY 40 AMP 5) SHOWER APPEARS TO HAVE NO "P" TRAP. EXPOSE ALL PLUMBING 6) EXPOSE ALL ELECTRICAL 7) MAIN HOUSE BEDROOMS MUST HAVE AT LEAST BATTERY OPERATED SMOKE DETECTORS 8) BATHROOM REQUIRES GFCI CIRCUIT 9) ELECTRIC OUTLETS REQUIRED WITHIN 6 FEET OF DOOR |
|
| 10/29/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920*/ 1) PROPERTY LOCKED. NO ACCESS 2) NEXT FAILURE YOU WILL BE CHARGED A REINSPECTION FEE. CALLED PHONE NUMBER LISTED PER MESSAGE. NO ONE AT THAT NUMBER |
|
| 10/28/2004 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*/ 1) CALLED AND LEFT MESSAGE AT 8:15 AM TO MEET FOR INSPECTION AT 9:00 AM. RETURNED AT 9:00 AM-HOUSE IS STILL LOCKED AND NO NONE IS HERE TO LET ME IN. PLEASE RESCHEDULE INSPECTION AND ARRANGE TO MEET INSPECTOR ON SITE |