Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04CM02546
Permit Details
Apply Date:
06/07/2004
Applicant:
KURT FRIMODIG
Description:
NEW SHELL RETAIL 90' x 75' SHELL BUILDING, MASONRY W/ TRUSS ROOF
Architects:
- KUBICEK, ROBERT W ARCHITECTS & ASSOCIATES
Contractors:
- RIO WEST DEVELOPMENT AND CONSTRU
Permit Reviews
Permit Number - T04CM02546
Permit Status: Final
Permit Description: NEW SHELL RETAIL
90' x 75' SHELL BUILDING, MASONRY W/ TRUSS ROOF
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/22/2005 | 3RD PARTY REVIEW-REVISION/OTHER | 04/21/2005 | COMPLETED |
| 06/07/2004 | PLANS OK TO SUBMIT - 3RD PARTY | 06/07/2004 | COMPLETED |
| 06/07/2004 | 3RD PARTY REVIEW-COMMERCIAL | 09/29/2004 | COMPLETED |
| 09/29/2004 | POST 3RD PARTY REVIEW | 10/15/2004 | COMPLETED |
| 10/15/2004 | RESUBMITTAL | 12/01/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T04CM02546
Permit Status: Final
Permit Description: NEW SHELL RETAIL
90' x 75' SHELL BUILDING, MASONRY W/ TRUSS ROOF
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 06/07/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T04CM02546
Permit Description: NEW SHELL RETAIL
90' x 75' SHELL BUILDING, MASONRY W/ TRUSS ROOF
Total Completed Inspections - 35
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2004 | ELECTRIC - UFER | RSUBA | Approved | IVRS - Inspection :* |
| 12/17/2004 | EXCAVATION/LAYOUT REBAR & ZON | LHANLY | Approved | IVRS - Inspection :* |
| 12/21/2004 | REINFORCED MASONRY PRE-GROUT | LHANLY | Approved | IVRS - Inspection :* |
| 12/29/2004 | ELECTRIC - CONSTRUCTION POWER | RSUBA | Approved | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH TEMP SERVICE |
| 03/11/2005 | PLUMBING - ROUGH, SOIL | JSTANLEY | Approved | IVRS - Inspection :* TEST OK ON UNDERGROUND SOIL PLEASE WRAP WASTE LINE IN SLAB |
| 05/04/2005 | FIRE SPKLR - UG PIPING FLUSH | LTHOMAS | Approved | |
| 05/04/2005 | FIRE SPKLR - UG, PIPING, HYDRO | LTHOMAS | Approved | |
| 06/30/2005 | ROOF NAILING | LHANLY | Approved | IVRS - Inspection :* |
| 07/22/2005 | PLUMBING - ROOF DRAINS | LHANLY | Approved | IVRS - Inspection :* |
| 08/01/2005 | BUILDING PRE-SLAB | LHANLY | Approved | IVRS - Inspection :* |
| 08/01/2005 | FRAMING | LHANLY | Approved | IVRS - Inspection :* |
| 08/10/2005 | SHEET ROCK NAILING | LHANLY | Approved | IVRS - Inspection :* |
| 09/14/2005 | ELECTRIC - UNDERGROUND | RSUBA | Approved | IVRS - Inspection : See detailed listing on site.| 999* |
| 09/29/2005 | MECHANICAL - ABOVE CEILING | JMILITEL | Approved | IVRS - Inspection :* R VALUES ON DUCT ARE OK AS PER PLANS |
| 10/04/2005 | BUILDING - FINAL | AMATHIES | Approved | IVRS - Inspection :* |
| 11/07/2005 | ELECTRIC - FINAL | RSUBA | Approved | IVRS - Inspection :* |
| 11/07/2005 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection :*PLEASE RECALL FOR INSPECTOR SUBA |
| 11/08/2005 | TEP CLEARANCE - AM | JKOZUCH | Approved | H.P # 4 ECO |
| 12/21/2005 | OUTDOOR LIGHTING FINAL | RSUBA | Approved | IVRS - Inspection :* |
| 12/21/2005 | ELECTRIC - CABLE DROP | RSUBA | Approved | IVRS - Inspection :* |
| 12/21/2005 | ELECTRIC - ABOVE CEILING | RSUBA | Approved | IVRS - Inspection :* |
| 12/21/2005 | U VALUE FOR WINDOW | LHANLY | Approved | IVRS - Inspection :* |
| 12/21/2005 | BUILDING ABOVE CEILING | LHANLY | Approved | IVRS - Inspection :* |
| 12/30/2005 | MECHANICAL - FINAL | JMILITEL | Approved | IVRS - Inspection :* HP -1 # 8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT HP 2,3 DISCONNECTS OVERFUSED . 25 AMP IS MAX CONNECT CONDENSATE DRAINS. PERMANENTLY IDENTIFY UNITS & HEAT STRIPS. PROVIDE COIL GUARD FOR HP -1 |
| 12/30/2005 | PLUMBING - FINAL | LHANLY | Approved | IVRS - Inspection :* 1) NEED PLAN SHOWING 100 AND 106 DELETED AND BACKFLOW CERTIFICATE |
| 12/30/2005 | FIRE - FINAL | LTHOMAS | Approved | |
| 12/30/2005 | FIRE SPKLR - FINAL | LTHOMAS | Approved | |
| 12/30/2005 | FIRE SPKLR - OH PIPING & HYDRO | LTHOMAS | Approved | |
| 08/25/2006 | MECHANICAL - INTERMEDIATE | JMILITEL | Approved | IVRS - Inspection :* |
| 08/28/2006 | PERMIT FINALED | BFLORES | Approved | |
| 08/28/2006 | PLUMBING - SEWER HCS CONNECT | RRICH | Approved | |
| 08/28/2006 | PLUMBING - YARD WTR LINE/TEST | RRICH | Approved | |
| 08/28/2006 | PLUMBING - ABOVE CEILING | RRICH | Approved | |
| 08/28/2006 | PLUMBING - INTERMEDIATE | RRICH | Approved | |
| 08/28/2006 | ELECTRIC - INTERMEDIATE | RSUBA | Approved |