Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T04CM02546
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/25/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/19/2006 | MECHANICAL - FINAL | Cancelled | CANCELLED PER CHARLIE OF RIO WEST DEVELOPMENT #250-5124 | |
| 06/19/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/30/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* HP -1 # 8 WIRE NOT ADEQUATE FOR 60 AMP CIRCUIT HP 2,3 DISCONNECTS OVERFUSED . 25 AMP IS MAX CONNECT CONDENSATE DRAINS. PERMANENTLY IDENTIFY UNITS & HEAT STRIPS. PROVIDE COIL GUARD FOR HP -1 |