Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Closed
Type:
COMMERCIAL OTHER
Apply Date:
04/30/2004
Applicant:
INTERSTATE MECHANICAL CORPORATIO
Description:
REPLACE:COOLING TOWER
Contractors:
  • INTERSTATE MECHANICAL CORPORATIO

Permit Reviews

Permit Number - T04CM01935
Permit Status: Closed
Permit Description: REPLACE:COOLING TOWER
Start Date Submittal Complete Date Status  
04/30/2004 COMMERCIAL TI 05/17/2004 COMPLETED Review Details
05/11/2004 RESUBMITTAL 05/17/2004 COMPLETED Review Details
05/17/2004 3RD PARTY REVIEW-COMMERCIAL 05/28/2004 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T04CM01935
Permit Status: Closed
Permit Description: REPLACE:COOLING TOWER
Total Outstanding Activity Conditions - 1
Date Name
04/30/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Closed
Permit Number: T04CM01935
Permite Description: REPLACE:COOLING TOWER
Total Outstanding Inspections - 6
Last Inspection Date Description Inspector Results Comments
FRAMING N/A Not Inspected
BUILDING - FINAL N/A Not Inspected
ELECTRIC - INTERMEDIATE N/A Not Inspected
PLUMBING - INTERMEDIATE N/A Not Inspected
PLUMBING - FINAL N/A Not Inspected
06/16/2004 ELECTRIC - FINAL N/A Partial Approval IVRS - Inspection :*/ 1) PLEASE VERIFY 600V RATING FOR PLENIUM CABLE. 2) CANNOT DOUBLE STACK LUGS IN DISCONNECT. 3) PLEASE PROVIDE 3RD PARTY LISTING FOR MCC CONNECTIONS AS PER ENGINEERS SPECIFICATIONS. LETTER IS NOT STAMPED. WE NEED A FIELD INSP. REPORT FOR THE INSTALLATION AND CONNECTIONS AT MCC. PROVIDE INSPECTOR WITH A COPY OF FIELD REPORT WITH STAMP OR CERTIFICATION.

Completed Inspections

Permit Status: Closed
Permit Number: T04CM01935
Permit Description: REPLACE:COOLING TOWER
Total Completed Inspections - 3
Date Description Inspector Results Comments
06/16/2004 MECHANICAL - FINAL JMILITEL Approved IVRS - Inspection :*
06/16/2004 MECHANICAL - PROGRESS JMILITEL Approved
06/16/2004 MECHANICAL - INTERMEDIATE JMILITEL Approved