Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
Permit Number - T04CM01935
Inspection Description - ELECTRIC - FINAL
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/16/2004 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*/ 1) PLEASE VERIFY 600V RATING FOR PLENIUM CABLE. 2) CANNOT DOUBLE STACK LUGS IN DISCONNECT. 3) PLEASE PROVIDE 3RD PARTY LISTING FOR MCC CONNECTIONS AS PER ENGINEERS SPECIFICATIONS. LETTER IS NOT STAMPED. WE NEED A FIELD INSP. REPORT FOR THE INSTALLATION AND CONNECTIONS AT MCC. PROVIDE INSPECTOR WITH A COPY OF FIELD REPORT WITH STAMP OR CERTIFICATION. | |
06/15/2004 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*/ NO WORK AT THIS TIME. |