Permit: T04CM01935

Parcel: 12510003A


Addresses:

3435 E BROADWAY BL


Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T04CM01935

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
06/16/2004 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*/ 1) PLEASE VERIFY 600V RATING FOR PLENIUM CABLE. 2) CANNOT DOUBLE STACK LUGS IN DISCONNECT. 3) PLEASE PROVIDE 3RD PARTY LISTING FOR MCC CONNECTIONS AS PER ENGINEERS SPECIFICATIONS. LETTER IS NOT STAMPED. WE NEED A FIELD INSP. REPORT FOR THE INSTALLATION AND CONNECTIONS AT MCC. PROVIDE INSPECTOR WITH A COPY OF FIELD REPORT WITH STAMP OR CERTIFICATION.
06/15/2004 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*/ NO WORK AT THIS TIME.