Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T04BU01251
Permit Details
Apply Date:
05/26/2004
Applicant:
CUTLER FIRE PROTECTION INC ,
Description:
FIRE SPKR:RELOCATE 9/ADD 7
Contractors:
- CUTLER FIRE PROTECTION INC ,
Outstanding Activity Conditions
Permit Number - T04BU01251
Permit Status: Expired
Permit Description: FIRE SPKR:RELOCATE 9/ADD 7
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/26/2004 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T04BU01251
Permite Description: FIRE SPKR:RELOCATE 9/ADD 7
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/29/2004 | FIRE SPKLR - FINAL | N/A | Not ready for Inspection | 1. Supervise water supply valves to fire sprinklers with lock and chain. 2. Provide hydraulic calculation data plate at riser. 3. Must test waterflow alarm. 4. Provide spare sprinkler head box with 17/32" orifice sprinklers. |