Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T04BU01251

Parcel: 13419042C


Addresses:

7160 E BROADWAY BL


Inspection Status: Not ready for Inspection

Inspection History: FIRE SPKLR - FINAL

Permit Number - T04BU01251

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
06/29/2004 FIRE SPKLR - FINAL Not ready for Inspection 1. Supervise water supply valves to fire sprinklers with lock and chain.
2. Provide hydraulic calculation data plate at riser.
3. Must test waterflow alarm.
4. Provide spare sprinkler head box with 17/32" orifice sprinklers.