Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address:
250 S VOZACK LN
Apply Date:
01/26/2004
Applicant:
KELLOGG FIRE N WIRE INC ,
Description:
FIRE SPRINKLER:ADD 68:INSTALL 271 LF 4"UNDERGROUND
Contractors:
  • KELLOGG FIRE N WIRE INC ,

Outstanding Activity Conditions

Permit Number - T04BU00193
Permit Status: Final
Permit Description: FIRE SPRINKLER:ADD 68:INSTALL 271 LF 4"UNDERGROUND
Total Outstanding Activity Conditions - 1
Date Name
01/26/2004 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T04BU00193
Permit Description: FIRE SPRINKLER:ADD 68:INSTALL 271 LF 4"UNDERGROUND
Total Completed Inspections - 5
Date Description Inspector Results Comments
05/12/2004 FIRE SPKLR - OH PIPING & HYDRO LTHOMAS Approved
07/21/2004 FIRE SPKLR - UG, PIPING, HYDRO LTHOMAS Approved 1) NEED FLUSH
11/19/2004 FIRE SPKLR - UG PIPING FLUSH LTHOMAS Approved
12/03/2004 FIRE SPKLR - FINAL CSCHULTZ Approved Add sprinkler heads in the following areas:
1.) New hallway closet
2.) Bedroom #1 closet
3.) Bedroom #3 2 closets
4.) Between bedrooms #4 & 5 bathroom relocate head to cover properly or add head for coverage.
5.) Bedroom #6 bathroom
6.) Closet in living room
7.) Bedroom #9 2 closets
8.) Main hallway closet
9.) Bedroom #7 as per plans remove sidewall and replace with pendent.
10.) Label riser parts
11.) Add spare sprinkler head box.
04/22/2005 PERMIT FINALED LJACKSON Approved