Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T04BU00193
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/11/2005 | FIRE SPKLR - FINAL | Approved | ||
02/24/2005 | FIRE SPKLR - FINAL | Not ready for Inspection | Needs as builts plans submitted for fire sprinklers | |
12/03/2004 | FIRE SPKLR - FINAL | Denied | Add sprinkler heads in the following areas: 1.) New hallway closet 2.) Bedroom #1 closet 3.) Bedroom #3 2 closets 4.) Between bedrooms #4 & 5 bathroom relocate head to cover properly or add head for coverage. 5.) Bedroom #6 bathroom 6.) Closet in living room 7.) Bedroom #9 2 closets 8.) Main hallway closet 9.) Bedroom #7 as per plans remove sidewall and replace with pendent. 10.) Label riser parts 11.) Add spare sprinkler head box. |