Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
6525 E CALLE BETELGEUX
Apply Date:
10/17/2003
Applicant:
ATLANTIS COOLING & HEATING INC *T
Description:
INSTALL:A/C AND FURNACE (APA)
Contractors:
  • ATLANTIS COOLING & HEATING INC *T

Outstanding Activity Conditions

Permit Number - T03ME00593
Permit Status: Expired
Permit Description: INSTALL:A/C AND FURNACE (APA)
Total Outstanding Activity Conditions - 1
Date Name
10/17/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03ME00593
Permite Description: INSTALL:A/C AND FURNACE (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
10/23/2003 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*/ 1) GAS SHUT OFF VALVE IS NOT ACCESSABLE. RELOCATE AS NEEDED. 2) CONDENSOR IS OVERFUSED AT 45 AMP. 35 AMP IS MAX FUSE SIZE. 3) USE SUN RESISTANT CONTROL WIRE OR USE CONDUIT. RECALL FOR INSPECTION.

Documents

File Name Document Type  
None DOCUMENTS VIEW