Permit: T03ME00593
Permit Details
Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
6525 E CALLE BETELGEUX
Address NEW:
6525 E CALLE BETELGEUX
Apply Date:
10/17/2003
Applicant:
ATLANTIS COOLING & HEATING INC *T
Description:
INSTALL:A/C AND FURNACE (APA)
Contractors:
- ATLANTIS COOLING & HEATING INC *T
Outstanding Activity Conditions
Permit Number - T03ME00593
Permit Status: Expired
Permit Description: INSTALL:A/C AND FURNACE (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/17/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03ME00593
Permite Description: INSTALL:A/C AND FURNACE (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2003 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999*/ 1) GAS SHUT OFF VALVE IS NOT ACCESSABLE. RELOCATE AS NEEDED. 2) CONDENSOR IS OVERFUSED AT 45 AMP. 35 AMP IS MAX FUSE SIZE. 3) USE SUN RESISTANT CONTROL WIRE OR USE CONDUIT. RECALL FOR INSPECTION. |