Permit: T03ME00593

Parcel: 135022320

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/23/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) GAS SHUT OFF VALVE IS NOT ACCESSABLE. RELOCATE AS NEEDED. 2) CONDENSOR IS OVERFUSED AT 45 AMP. 35 AMP IS MAX FUSE SIZE. 3) USE SUN RESISTANT CONTROL WIRE OR USE CONDUIT. RECALL FOR INSPECTION.