Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) GAS SHUT OFF VALVE IS NOT ACCESSABLE. RELOCATE AS NEEDED. 2) CONDENSOR IS OVERFUSED AT 45 AMP. 35 AMP IS MAX FUSE SIZE. 3) USE SUN RESISTANT CONTROL WIRE OR USE CONDUIT. RECALL FOR INSPECTION. |