Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address NEW:
230 W IRVINGTON RD
Apply Date:
09/23/2003
Applicant:
TUCSON AIR *C,
Description:
REPLACE:A/C & FURNACE (APA)
Contractors:
  • TUCSON AIR *C,

Outstanding Activity Conditions

Permit Number - T03ME00544
Permit Status: Expired
Permit Description: REPLACE:A/C & FURNACE (APA)
Total Outstanding Activity Conditions - 1
Date Name
09/23/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03ME00544
Permite Description: REPLACE:A/C & FURNACE (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
09/29/2003 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*/1) MAX FUSE SIZE - UNIT DATA PLATE, 50 AMPS - UNIT FUSED AT 60. #8 COPPER ONLY GOOD FOR 50AMPS. WHY DO YOU HAVE 60 AMP FUSES?? 2) PVC CONDENSATE, NOT PAINTED, WHY ISN'T THERE A TRAP. 3) THIS A COMBINATION GAS - ELECT. GAS LINE NOT RUN OR CONNECTED? 4) NEED ELECTRICAL PERMIT FOR NEW A/C CICUIT, PANEL TO UNIT.

Documents

File Name Document Type  
None DOCUMENTS VIEW