Permit: T03ME00544

Parcel: 12008643A


Addresses:

230 W IRVINGTON RD

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
09/29/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/1) MAX FUSE SIZE - UNIT DATA PLATE, 50 AMPS - UNIT FUSED AT 60. #8 COPPER ONLY GOOD FOR 50AMPS. WHY DO YOU HAVE 60 AMP FUSES?? 2) PVC CONDENSATE, NOT PAINTED, WHY ISN'T THERE A TRAP. 3) THIS A COMBINATION GAS - ELECT. GAS LINE NOT RUN OR CONNECTED? 4) NEED ELECTRICAL PERMIT FOR NEW A/C CICUIT, PANEL TO UNIT.