Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/29/2003 |
MECHANICAL - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) MAX FUSE SIZE - UNIT DATA PLATE, 50 AMPS - UNIT FUSED AT 60. #8 COPPER ONLY GOOD FOR 50AMPS. WHY DO YOU HAVE 60 AMP FUSES?? 2) PVC CONDENSATE, NOT PAINTED, WHY ISN'T THERE A TRAP. 3) THIS A COMBINATION GAS - ELECT. GAS LINE NOT RUN OR CONNECTED? 4) NEED ELECTRICAL PERMIT FOR NEW A/C CICUIT, PANEL TO UNIT. |