Description:
retrofit gas furnace
Contractors:
  • AMBIENT AIR HEATING AND COOLING L L C

Outstanding Activity Conditions

Permit Number - T03ME00313
Permit Status: Expired
Permit Description: retrofit gas furnace
Total Outstanding Activity Conditions - 1
Date Name
06/11/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03ME00313
Permite Description: retrofit gas furnace
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
06/19/2003 MECHANICAL - FINAL N/A Denied IVRS - Inspection 0999*/1) USE A CONNECTOR WHERE ELEC WIRES PENETRATE THE CABINET OF FURNACE; 2) PROVIDE MIN 3 SECREWS IN EACH JOINT ON VENT CONNECTOR. TAPING OF JOINTS IS NOT NECESSARY - GLUE ON TAPE WILL DRY OUT; 3) FURNACE VENT CANNOT TERMINATE INTO A TTOP. BE SURE VENT IS DOUBLE WALL THRU CEILING, ATTIC, AND ROOF. USE AN APPROVED CAP AND FLASHING. RECALL FOR INSPECTION.