Permit: T03ME00313

Parcel: 128121360


Addresses:

4834 E 17TH ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/19/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/1) USE A CONNECTOR WHERE ELEC WIRES PENETRATE THE CABINET OF FURNACE; 2) PROVIDE MIN 3 SECREWS IN EACH JOINT ON VENT CONNECTOR. TAPING OF JOINTS IS NOT NECESSARY - GLUE ON TAPE WILL DRY OUT; 3) FURNACE VENT CANNOT TERMINATE INTO A TTOP. BE SURE VENT IS DOUBLE WALL THRU CEILING, ATTIC, AND ROOF. USE AN APPROVED CAP AND FLASHING. RECALL FOR INSPECTION.