Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
250 N JACS PL
Address NEW:
250 N JACS PL
Apply Date:
06/09/2003
Applicant:
RINCON AIR COND AND HEAT,*C,*P
Description:
INSTALL:3 TON HEATPUMP (APA)
Contractors:
  • RINCON AIR COND AND HEAT,*C,*P

Outstanding Activity Conditions

Permit Number - T03ME00308
Permit Status: Expired
Permit Description: INSTALL:3 TON HEATPUMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
06/09/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03ME00308
Permite Description: INSTALL:3 TON HEATPUMP (APA)
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/10/2003 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection 0000*/ 1) UNIT IS OVERFUSED AT 40 AMP. 35 AMP IS MAXIMUM FUSE SIZE. RECALL FOR INSPECTION

Documents

File Name Document Type  
None DOCUMENTS VIEW