Permit: T03ME00308

Parcel: 13345064A


Addresses:

250 N JACS PL


Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Permit Number - T03ME00308

Inspection Description - MECHANICAL - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
07/10/2003 MECHANICAL - FINAL Partial Approval IVRS - Inspection 0000*/ 1) UNIT IS OVERFUSED AT 40 AMP. 35 AMP IS MAXIMUM FUSE SIZE. RECALL FOR INSPECTION