Permit: T03ME00275
Permit Details
Apply Date:
05/29/2003
Applicant:
JUSTICE DJ
Description:
r/r a/c gas pack
Contractors:
- QUALIFIED MECHANICAL CONTRACTORS,*C
Outstanding Activity Conditions
Permit Number - T03ME00275
Permit Status: Expired
Permit Description: r/r a/c gas pack
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/29/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03ME00275
Permite Description: r/r a/c gas pack
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2003 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999*/ 1) CRIMP ON SINGLE WALL VENT CONNECTOR RAN BACKWARDS. SHOULD GO WITH AIR FLOW. PROVIDE MINIMUM 3 SCREWS IN EACH JOINT ON VENT CONNECTOR. PROVIDE MINIMUM 6" CLEARANCE WHERE PVC PASSES IN FRONT OF FURNACE VENT 1" IF USING DOUBLE WALL 2) PROVIDE A TRAP ON CONDENSATE DRAIN LINE 3) PROVIDE ROMEX CONNECTOR WHERE ELECTRIC WIRES PENETRATE THE CABINET OF THE CONDENSING UNIT. RECALL FOR INSPECTION |