Permit: T03ME00275

Parcel: 136241240


Addresses:

6872 E MARY DR

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/06/2003 MECHANICAL - FINAL Denied IVRS - Inspection 0999*/ 1) CRIMP ON SINGLE WALL VENT CONNECTOR RAN BACKWARDS. SHOULD GO WITH AIR FLOW. PROVIDE MINIMUM 3 SCREWS IN EACH JOINT ON VENT CONNECTOR. PROVIDE MINIMUM 6" CLEARANCE WHERE PVC PASSES IN FRONT OF FURNACE VENT 1" IF USING DOUBLE WALL 2) PROVIDE A TRAP ON CONDENSATE DRAIN LINE 3) PROVIDE ROMEX CONNECTOR WHERE ELECTRIC WIRES PENETRATE THE CABINET OF THE CONDENSING UNIT. RECALL FOR INSPECTION