Permit: T03EL02422
Permit Details
Apply Date:
12/17/2003
Applicant:
CORRECT CONNECTIONS INC *C
Description:
UPGRADE:ELECTRIC TO 125AMP (APA)
Contractors:
- CORRECT CONNECTIONS INC *C
Outstanding Activity Conditions
Permit Number - T03EL02422
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 125AMP (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/17/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T03EL02422
Permit Description: UPGRADE:ELECTRIC TO 125AMP (APA)
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2003 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection 0999*/ 1) NEED TO VERIFY WATER AND GAS BOND. 2) UNCOVER 2ND GROUND ROD CONNECTION. 3) SUPPORT #4 BARE COPPER BELOW SERVICE TO RODS [TO WALL]. 4) HAD TO TAPE EXPOSE COPPER IN 4 11/16 J-BOX, WAS PENETRATING THRU BLACK TAPE. REDO SPLICES. 5) THERE NEEDS TO BE AN A/C PERMIT BEFORE ANY CLEARANCE WILL BE MADE. 6) LABEL PANEL SCHEDULE. |
| 01/13/2004 | PERMIT FINALED | RMAJUTA | Approved | |
| 01/13/2004 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | IVRS - Inspection 0000* |
| 01/13/2004 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | IVRS - Inspection 0000* |