Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
SINGLE FAMILY OTHER
Address NEW:
5369 E WILLARD ST
Apply Date:
12/17/2003
Applicant:
CORRECT CONNECTIONS INC *C
Description:
UPGRADE:ELECTRIC TO 125AMP (APA)
Contractors:
  • CORRECT CONNECTIONS INC *C

Outstanding Activity Conditions

Permit Number - T03EL02422
Permit Status: Final
Permit Description: UPGRADE:ELECTRIC TO 125AMP (APA)
Total Outstanding Activity Conditions - 1
Date Name
12/17/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T03EL02422
Permit Description: UPGRADE:ELECTRIC TO 125AMP (APA)
Total Completed Inspections - 4
Date Description Inspector Results Comments
12/19/2003 ELECTRIC - FINAL RMAJUTA Approved IVRS - Inspection 0999*/ 1) NEED TO VERIFY WATER AND GAS BOND. 2) UNCOVER 2ND GROUND ROD CONNECTION. 3) SUPPORT #4 BARE COPPER BELOW SERVICE TO RODS [TO WALL]. 4) HAD TO TAPE EXPOSE COPPER IN 4 11/16 J-BOX, WAS PENETRATING THRU BLACK TAPE. REDO SPLICES. 5) THERE NEEDS TO BE AN A/C PERMIT BEFORE ANY CLEARANCE WILL BE MADE. 6) LABEL PANEL SCHEDULE.
01/13/2004 PERMIT FINALED RMAJUTA Approved
01/13/2004 ELECTRIC - INTERMEDIATE RMAJUTA Approved IVRS - Inspection 0000*
01/13/2004 ELECTRIC - UNDERGROUND RMAJUTA Approved IVRS - Inspection 0000*

Documents

File Name Document Type  
None DOCUMENTS VIEW