Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/13/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 01/14/04AM |
| 12/19/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ 1) NEED TO VERIFY WATER AND GAS BOND. 2) UNCOVER 2ND GROUND ROD CONNECTION. 3) SUPPORT #4 BARE COPPER BELOW SERVICE TO RODS [TO WALL]. 4) HAD TO TAPE EXPOSE COPPER IN 4 11/16 J-BOX, WAS PENETRATING THRU BLACK TAPE. REDO SPLICES. 5) THERE NEEDS TO BE AN A/C PERMIT BEFORE ANY CLEARANCE WILL BE MADE. 6) LABEL PANEL SCHEDULE. |