Permit: T03EL02422

Parcel: 121121790


Addresses:

5369 E WILLARD ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/13/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 01/14/04AM
12/19/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ 1) NEED TO VERIFY WATER AND GAS BOND. 2) UNCOVER 2ND GROUND ROD CONNECTION. 3) SUPPORT #4 BARE COPPER BELOW SERVICE TO RODS [TO WALL]. 4) HAD TO TAPE EXPOSE COPPER IN 4 11/16 J-BOX, WAS PENETRATING THRU BLACK TAPE. REDO SPLICES. 5) THERE NEEDS TO BE AN A/C PERMIT BEFORE ANY CLEARANCE WILL BE MADE. 6) LABEL PANEL SCHEDULE.