Permit: T03EL02386
Permit Details
Status:
Final
Type:
SINGLE FAMILY OTHER
Address:
2066 E HANCOCK VISTA
Address NEW:
2066 E HANCOCK VISTA
Apply Date:
12/10/2003
Applicant:
EDDIE CRUZ
Description:
ELECTRIC:UPGRADE 100AMPS
Permit Reviews
Permit Number - T03EL02386
Permit Status: Final
Permit Description: ELECTRIC:UPGRADE 100AMPS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 12/10/2003 | ELECTRICAL | 12/10/2003 | COMPLETED |
| 12/14/2004 | ELECTRICAL | 12/14/2004 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03EL02386
Permit Status: Final
Permit Description: ELECTRIC:UPGRADE 100AMPS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 12/10/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T03EL02386
Permit Description: ELECTRIC:UPGRADE 100AMPS
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/30/2003 | ELECTRIC - SERVICE UPGRADE | MCAPISTR | Approved | IVRS - Inspection 0245*/ THE FOLLOWING NEED CORRECTION. 1) THE ADDRESS ON THE SERVICE PANEL MUST BE OF METAL. DO NOT USE PEN, PENCIL, OR MAGIC MARKER. THESE FADE AWAY. 2) THE METER MUST BE LOCATED NOT HIGHER THAN 6'3" FROM THE GROUND TO THE CENTER OF METER.3) THE PANEL MUST BE READILY ACCESSIBLE. REMOVE ALL BRUSH AND OTHER OBSTACLES TO PROVIDE THIS CLEARANCE TO THE FRONT AND 30" TO THE SIDE. 4) PROVIDE TWO STRAPS ON THE RISER CONDUIT. ONE AT LEAST 8" FROM THE TOP OF THE BOX. |
| 12/23/2004 | ELECTRIC - FINAL | DSANTACR | Approved | IVRS - Inspection :* 1) OK TO CLEAR INCREASE |
| 12/23/2004 | ELECTRIC - INTERMEDIATE | DSANTACR | Approved | IVRS - Inspection :* |
| 12/23/2004 | ELECTRIC - UNDERGROUND | DSANTACR | Approved | IVRS - Inspection :* |
| 12/27/2004 | PERMIT FINALED | JWEATHER | Approved | |
| 12/27/2004 | TEP CLEARANCE - AM | SLONG | Approved | INC; UPGRADE TO 100A |