Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/23/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/28/2004 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 12/30/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*/ THE FOLLOWING NEED CORRECTION. 1) THE ADDRESS ON THE SERVICE PANEL MUST BE OF METAL. DO NOT USE PEN, PENCIL, OR MAGIC MARKER. THESE FADE AWAY. 2) THE METER MUST BE LOCATED NOT HIGHER THAN 6'3" FROM THE GROUND TO THE CENTER OF METER.3) THE PANEL MUST BE READILY ACCESSIBLE. REMOVE ALL BRUSH AND OTHER OBSTACLES TO PROVIDE THIS CLEARANCE TO THE FRONT AND 30" TO THE SIDE. 4) PROVIDE TWO STRAPS ON THE RISER CONDUIT. ONE AT LEAST 8" FROM THE TOP OF THE BOX. |