Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Address:
130 S PLUMER AV
Apply Date:
11/07/2003
Applicant:
FRED CONTRERAS
Description:
RECONNECT:ELECTRIC: TREE LOT

Outstanding Activity Conditions

Permit Number - T03EL02202
Permit Status: Expired
Permit Description: RECONNECT:ELECTRIC: TREE LOT
Total Outstanding Activity Conditions - 1
Date Name
11/07/2003 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T03EL02202
Permite Description: RECONNECT:ELECTRIC: TREE LOT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
11/13/2003 ELECTRIC - RECONNECT N/A Denied IVRS - Inspection 0999*/ ELECTRICAL L-11 OR K-11 CONTRACTOR TO MAKE REPAIRS, ADJUSTMENTS ETC. 1) ALL TEMP LIGHTING AND CONSTRUCTION TRAILER TO BE SET UP. 2) PROPER METAL ADDRESS TAG REQUIRED AT ELECTRICAL METER. 3) IDENTIFY THE THREE SERVICE DISCONNECTS TO MATCH SERVICE AND SUB-PANEL 4) ADDRESS (SEE #2) TO BE 130 S. PLUMER. 5) CHECK VOLTAGES - (COLOR CODE ON SERVICE INDICATIVE OF 480 VOLTS) 6) PROVIDE ONE LINE DIAGRAM SKETCH OF SERVICE EQUIPMENT AND SUB-PANELS. 7) NEUTRAL AT SERVICE DISCONNECT NOT BONDED. PLEASE BOND. RECALL INSPECTION WHEN READY.
11/13/2003 ELECTRIC - FINAL N/A Not ready for Inspection IVRS - Inspection 0000*