Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 11/13/2003 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*/ ELECTRICAL L-11 OR K-11 CONTRACTOR TO MAKE REPAIRS, ADJUSTMENTS ETC. 1) ALL TEMP LIGHTING AND CONSTRUCTION TRAILER TO BE SET UP. 2) PROPER METAL ADDRESS TAG REQUIRED AT ELECTRICAL METER. 3) IDENTIFY THE THREE SERVICE DISCONNECTS TO MATCH SERVICE AND SUB-PANEL 4) ADDRESS (SEE #2) TO BE 130 S. PLUMER. 5) CHECK VOLTAGES - (COLOR CODE ON SERVICE INDICATIVE OF 480 VOLTS) 6) PROVIDE ONE LINE DIAGRAM SKETCH OF SERVICE EQUIPMENT AND SUB-PANELS. 7) NEUTRAL AT SERVICE DISCONNECT NOT BONDED. PLEASE BOND. RECALL INSPECTION WHEN READY. |
| 11/10/2003 |
ELECTRIC - RECONNECT |
|
Not ready for Inspection |
IVRS - Inspection 0000* |