Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
Permit Number - T03EL02202
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/13/2003 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*/ ELECTRICAL L-11 OR K-11 CONTRACTOR TO MAKE REPAIRS, ADJUSTMENTS ETC. 1) ALL TEMP LIGHTING AND CONSTRUCTION TRAILER TO BE SET UP. 2) PROPER METAL ADDRESS TAG REQUIRED AT ELECTRICAL METER. 3) IDENTIFY THE THREE SERVICE DISCONNECTS TO MATCH SERVICE AND SUB-PANEL 4) ADDRESS (SEE #2) TO BE 130 S. PLUMER. 5) CHECK VOLTAGES - (COLOR CODE ON SERVICE INDICATIVE OF 480 VOLTS) 6) PROVIDE ONE LINE DIAGRAM SKETCH OF SERVICE EQUIPMENT AND SUB-PANELS. 7) NEUTRAL AT SERVICE DISCONNECT NOT BONDED. PLEASE BOND. RECALL INSPECTION WHEN READY. | |
11/10/2003 | ELECTRIC - RECONNECT | Not ready for Inspection | IVRS - Inspection 0000* |