Permit: T03EL02080
Permit Details
Apply Date:
10/22/2003
Applicant:
A AMERICAN ELECTRICAL SERVICES
Description:
UPGRADE:ELECTRIC TO 100AMP
Contractors:
- A AMERICAN ELECTRICAL SERVICES
Permit Reviews
Permit Number - T03EL02080
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC TO 100AMP
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/22/2003 | ELECTRICAL | 10/22/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03EL02080
Permit Status: Expired
Permit Description: UPGRADE:ELECTRIC TO 100AMP
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/22/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03EL02080
Permite Description: UPGRADE:ELECTRIC TO 100AMP
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2003 | ELECTRIC - FINAL | N/A | Denied | PLEASE VERIFY THAT ALL LIGHTING CIRCUITS ARE IN FACT RATED 20 AMPS. 1/2" EMT CONNECTOR LOOSE. TOP ENTRY ON RIGHT; WIRE RUN THROUGH THIS AREA CAUSE UTILITY CONDUCTOR TO INTERMIX WITH CUSTOMER WIRING. TOP ENTRY K.O. (LEFT) - NEED K.O. SEAL. Q.P. BREAKER INSTALLED NOT ON U.L. LIST OF ACCEPTABLE BREAKERS. EXPOSE GROUND ROD CONNECTIONS. |