Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/23/2003 |
ELECTRIC - FINAL |
|
Denied |
PLEASE VERIFY THAT ALL LIGHTING CIRCUITS ARE IN FACT RATED 20 AMPS. 1/2" EMT CONNECTOR LOOSE. TOP ENTRY ON RIGHT; WIRE RUN THROUGH THIS AREA CAUSE UTILITY CONDUCTOR TO INTERMIX WITH CUSTOMER WIRING. TOP ENTRY K.O. (LEFT) - NEED K.O. SEAL. Q.P. BREAKER INSTALLED NOT ON U.L. LIST OF ACCEPTABLE BREAKERS. EXPOSE GROUND ROD CONNECTIONS. |