Permit: T03EL02080

Parcel: 126120880


Addresses:

4644 E HOLMES ST

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/23/2003 ELECTRIC - FINAL Denied PLEASE VERIFY THAT ALL LIGHTING CIRCUITS ARE IN FACT RATED 20 AMPS. 1/2" EMT CONNECTOR LOOSE. TOP ENTRY ON RIGHT; WIRE RUN THROUGH THIS AREA CAUSE UTILITY CONDUCTOR TO INTERMIX WITH CUSTOMER WIRING. TOP ENTRY K.O. (LEFT) - NEED K.O. SEAL. Q.P. BREAKER INSTALLED NOT ON U.L. LIST OF ACCEPTABLE BREAKERS. EXPOSE GROUND ROD CONNECTIONS.