Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T03EL02074
Permit Details
Apply Date:
10/22/2003
Applicant:
ESSNER ELECTRIC
Description:
INSTALL:NEW ELECTRIC METER
Contractors:
- ESSNER ELECTRIC
Permit Reviews
Permit Number - T03EL02074
Permit Status: Final
Permit Description: INSTALL:NEW ELECTRIC METER
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
10/22/2003 | ELECTRICAL | 10/23/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03EL02074
Permit Status: Final
Permit Description: INSTALL:NEW ELECTRIC METER
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
10/22/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T03EL02074
Permit Description: INSTALL:NEW ELECTRIC METER
Total Completed Inspections - 5
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/04/2003 | ELECTRIC - SERVICE UPGRADE | RHOLLAND | Approved | IVRS - Inspection 0999*/ 1) CLEAN SURFACE UNDER LUG 250.12 2) SHEET METAL SCREWS NOT ALLOWED 250.8 3) NEUTRAL GROUNDED CONDUCTORS TO BE IDENTIFIED CORRECTLY 500.6 4) RISER SUPPORTS TO BE 1/4" MINIMUM 5) FINISH ITEMS #3, 5, 6 AND 8 OF PREVIOUS INSPECTION |
11/04/2003 | ELECTRIC - INTERMEDIATE | RHOLLAND | Approved | IVRS - Inspection 0999* |
11/04/2003 | ELECTRIC - UNDERGROUND | RHOLLAND | Approved | IVRS - Inspection 0999* |
12/11/2003 | ELECTRIC - FINAL | RHOLLAND | Approved | IVRS - Inspection 0935* 1) SUPPORT BOND CONDUCTOR TO BUILDING ON WALL & ROOF. 2) #3 INSPECTION DATED 10-27-03 A REFEE HAS BEEN ACCESSED |
01/22/2004 | PERMIT FINALED | RHOLLAND | Approved |