Permit: T03EL02074

Parcel: 125110430


Addresses:

3828 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T03EL02074

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
01/21/2004 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
01/08/2004 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*/ 1) COMPLETE #1 OF PREVIOUS INSPECTION 2) TIGHTEN LOOSE BOND BUSHING LUG 3) RE-ANCHOR/ RE-SUPPORT CONDUIT ON WALL
11/04/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) CLEAN SURFACE UNDER LUG 250.12 2) SHEET METAL SCREWS NOT ALLOWED 250.8 3) NEUTRAL GROUNDED CONDUCTORS TO BE IDENTIFIED CORRECTLY 500.6 4) RISER SUPPORTS TO BE 1/4" MINIMUM 5) FINISH ITEMS #3, 5, 6 AND 8 OF PREVIOUS INSPECTION
10/27/2003 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*/ 1) THIS IS A SERVICE UPGRADE 2) A PERMANENT METAL ADDRESS LABEL IS NEEDED 3) ENTRANCES TO BE ACCESSIBLE AND SEALED ABOVE CURRENT CARRING PARTS 4) A NEW GROUNDING ELECTRODE SYSTEM TO BE INSTALLED WITH NEW SERVICE 5) GAS AND WATER BONDS ARE NEEDED 250.104 6) JUNCTION BOX ENCLOSURE TO BE BONDED 250.148 7) BLUE WIRE NUTS NOT LISTED FOR CONDUCTORS OF THIS SIZE 110.3 8) RISER TO HAVE 2 SUPPORTS BE LOW ROOF LINE (TEP) 9) LABEL BREAKERS 10) SUPPORT CONDUITS AS PER CODE 11) TIGHTEN LOOSE FITTINGS 12) GROUNDING EQUIPMENT CONDUCTOR COLOR TO BE ENTIRE LENGTH 250.119