Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T03EL02074
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/21/2004 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
01/08/2004 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*/ 1) COMPLETE #1 OF PREVIOUS INSPECTION 2) TIGHTEN LOOSE BOND BUSHING LUG 3) RE-ANCHOR/ RE-SUPPORT CONDUIT ON WALL | |
11/04/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*/ 1) CLEAN SURFACE UNDER LUG 250.12 2) SHEET METAL SCREWS NOT ALLOWED 250.8 3) NEUTRAL GROUNDED CONDUCTORS TO BE IDENTIFIED CORRECTLY 500.6 4) RISER SUPPORTS TO BE 1/4" MINIMUM 5) FINISH ITEMS #3, 5, 6 AND 8 OF PREVIOUS INSPECTION | |
10/27/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*/ 1) THIS IS A SERVICE UPGRADE 2) A PERMANENT METAL ADDRESS LABEL IS NEEDED 3) ENTRANCES TO BE ACCESSIBLE AND SEALED ABOVE CURRENT CARRING PARTS 4) A NEW GROUNDING ELECTRODE SYSTEM TO BE INSTALLED WITH NEW SERVICE 5) GAS AND WATER BONDS ARE NEEDED 250.104 6) JUNCTION BOX ENCLOSURE TO BE BONDED 250.148 7) BLUE WIRE NUTS NOT LISTED FOR CONDUCTORS OF THIS SIZE 110.3 8) RISER TO HAVE 2 SUPPORTS BE LOW ROOF LINE (TEP) 9) LABEL BREAKERS 10) SUPPORT CONDUITS AS PER CODE 11) TIGHTEN LOOSE FITTINGS 12) GROUNDING EQUIPMENT CONDUCTOR COLOR TO BE ENTIRE LENGTH 250.119 |