Permit: T03EL01971
Permit Details
Apply Date:
10/06/2003
Applicant:
BAYERS JAMES
Description:
RELOCATE:ELECTRIC METER BOX
Permit Reviews
Permit Number - T03EL01971
Permit Status: Final
Permit Description: RELOCATE:ELECTRIC METER BOX
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/06/2003 | ELECTRICAL | 10/06/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03EL01971
Permit Status: Final
Permit Description: RELOCATE:ELECTRIC METER BOX
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/06/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T03EL01971
Permit Description: RELOCATE:ELECTRIC METER BOX
Total Completed Inspections - 5
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2003 | ELECTRIC - FINAL | MCAPISTR | Approved | IVRS - Inspection 0245*/ CORRECTION REQUIRED: 1) PULL IN A GROUND WIRE FOR EACH SUB-PANEL SIZE ACCORDINGLY. 2) INSTALL BONDING BUSHING ON CONDUIT STUBS AT EACH END - MAIN PANEL AND HOUSE SUB PANEL. 3) INSTALL NEW #4 GROUND WIRE FROM HOUSE SUB-PANEL TO GAS PIPE (AT METER) AND COLD WATER LINE (SAME LOCATION). 4) ADD GROUND BARS AT EACH SUB-PANEL AND SEPERATE GROUND AND NUETRAL WIRES. |
| 10/23/2003 | ELECTRIC - SERVICE RELOCATION | MCAPISTR | Approved | IVRS - Inspection 0236* |
| 10/23/2003 | ELECTRIC - INTERMEDIATE | MCAPISTR | Approved | IVRS - Inspection 0245* |
| 10/23/2003 | ELECTRIC - UNDERGROUND | MCAPISTR | Approved | IVRS - Inspection 0245* |
| 01/16/2004 | PERMIT FINALED | MCAPISTR | Approved |