Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/15/2004 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/23/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ CORRECTION REQUIRED: 1) PULL IN A GROUND WIRE FOR EACH SUB-PANEL SIZE ACCORDINGLY. 2) INSTALL BONDING BUSHING ON CONDUIT STUBS AT EACH END - MAIN PANEL AND HOUSE SUB PANEL. 3) INSTALL NEW #4 GROUND WIRE FROM HOUSE SUB-PANEL TO GAS PIPE (AT METER) AND COLD WATER LINE (SAME LOCATION). 4) ADD GROUND BARS AT EACH SUB-PANEL AND SEPERATE GROUND AND NUETRAL WIRES. |
| 10/08/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/ PLEASE FURNISH THE FOLLOWING INFORMATION: 1) COPIES OF THE BLDG PERMIT FOR THE TWO CAR GARAGE AND SHOP/APARTMENT. THIS STRUCTURE APPEARS TO BE NEW. 2) COPIES OF PLANNING DEPT. APPROVAL OF THE GARAGE BLDG. 3) APPROVED PLANS WHICH INCLUDE SITE PLAN, BLDG ETC. 4) WRITTEN STATEMENT/LETTER FROM TUCSON ELECTRIC APPROVING 2ND METER AND SERVICE LATERAL TO ONE LOT. |