Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T03EL01971

Parcel: 113101380


Addresses:

1745 E SILVER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/15/2004 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/23/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0245*/ CORRECTION REQUIRED: 1) PULL IN A GROUND WIRE FOR EACH SUB-PANEL SIZE ACCORDINGLY. 2) INSTALL BONDING BUSHING ON CONDUIT STUBS AT EACH END - MAIN PANEL AND HOUSE SUB PANEL. 3) INSTALL NEW #4 GROUND WIRE FROM HOUSE SUB-PANEL TO GAS PIPE (AT METER) AND COLD WATER LINE (SAME LOCATION). 4) ADD GROUND BARS AT EACH SUB-PANEL AND SEPERATE GROUND AND NUETRAL WIRES.
10/08/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*/ PLEASE FURNISH THE FOLLOWING INFORMATION: 1) COPIES OF THE BLDG PERMIT FOR THE TWO CAR GARAGE AND SHOP/APARTMENT. THIS STRUCTURE APPEARS TO BE NEW. 2) COPIES OF PLANNING DEPT. APPROVAL OF THE GARAGE BLDG. 3) APPROVED PLANS WHICH INCLUDE SITE PLAN, BLDG ETC. 4) WRITTEN STATEMENT/LETTER FROM TUCSON ELECTRIC APPROVING 2ND METER AND SERVICE LATERAL TO ONE LOT.