Permit: T03EL01537
Permit Details
Apply Date:
08/05/2003
Applicant:
STURGEON ELECTRIC COMPANY,*C
Description:
REPLACE:ELECTRIC METER (APA)
Contractors:
- STURGEON ELECTRIC COMPANY,*C
Outstanding Activity Conditions
Permit Number - T03EL01537
Permit Status: Final
Permit Description: REPLACE:ELECTRIC METER (APA)
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/05/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T03EL01537
Permit Description: REPLACE:ELECTRIC METER (APA)
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/06/2003 | ELECTRIC - INTERMEDIATE | RMAJUTA | Approved | |
08/06/2003 | ELECTRIC - UNDERGROUND | RMAJUTA | Approved | |
08/08/2003 | PERMIT FINALED | RMAJUTA | Approved | |
08/08/2003 | ELECTRIC - FINAL | RMAJUTA | Approved | IVRS - Inspection 0000*SENT TO TEP ON 08/08AM 1ST INSPECTION 250-94 NEC 99- BONDING JUMPERS SHALL BE USED AROUND CONCENTRIC OR ECCENTRIC KNOCKOUTS THAT SERVICE CONDUCTORS PASS THUR. NEED A GROUNDING BUSHING OR ANOTHER METHOD PERHAPS A GROUND CLAMP BELOW ENCOSURE WITH A 3/0 CU TO CAN OR A GROUND CLAMPS WHEEL CAN BE PUT AROUND GROUND PIPE AND HAVE EXISTING UFER TIE INTO IT. 2) 12:00PM STURGEON HAS REPAIRED PROBLEM OK TO CLEAR SERVICE REPLACEMENT 8 UNITS BLDG B UNITS 1,2,5,6,9,10,13,14 ECO. 2090 FINAL ELECTRIC APPROVED. |