Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/08/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 08/08AM 1ST INSPECTION 250-94 NEC 99- BONDING JUMPERS SHALL BE USED AROUND CONCENTRIC OR ECCENTRIC KNOCKOUTS THAT SERVICE CONDUCTORS PASS THUR. NEED A GROUNDING BUSHING OR ANOTHER METHOD PERHAPS A GROUND CLAMP BELOW ENCOSURE WITH A 3/0 CU TO CAN OR A GROUND CLAMPS WHEEL CAN BE PUT AROUND GROUND PIPE AND HAVE EXISTING UFER TIE INTO IT. 2) 12:00PM STURGEON HAS REPAIRED PROBLEM OK TO CLEAR SERVICE REPLACEMENT 8 UNITS BLDG B UNITS 1,2,5,6,9,10,13,14 ECO. 2090 FINAL ELECTRIC APPROVED. |