Permit: T03EL01419
Permit Details
Apply Date:
07/18/2003
Applicant:
BARRERA JESUS
Description:
ELECTRIC:RELOCATE SERVICE
Permit Reviews
Permit Number - T03EL01419
Permit Status: Expired
Permit Description: ELECTRIC:RELOCATE SERVICE
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 07/18/2003 | ELECTRICAL | 07/18/2003 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T03EL01419
Permit Status: Expired
Permit Description: ELECTRIC:RELOCATE SERVICE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/18/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T03EL01419
Permite Description: ELECTRIC:RELOCATE SERVICE
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2003 | ELECTRIC - FINAL | N/A | Partial Approval | IVRS - Inspection 0000* 1) INSTALL A SEALING LOCKNUT AT 3/4" E.M.T. CONNECTION AT SERVICE PANEL. 2) I.D. GROUNDING CONDUCTOR AT BOND BUSHIN EITHER GREEN OR BARE COPPER. 3) NEED NEUTRAL FOR EACH A & B PHASE CIRCUIT (8 CIRCUITS NEED 4 NEUTRALS) OR REMOVE 2 CIRCUITS AT OLD SERVICE LOCATION.. 4) PROTECT EXSISTING #14 WIRE AT 15 AMPS MAXIUM CIRCUIT BREAKER. 5) USE PROPER BREAKER AT NEW SERVICE PANEL PER LISTING. |
| 10/14/2003 | ELECTRIC - SERVICE RELOCATION | N/A | Partial Approval | IVRS - Inspection 0000*/ 1) WILL APPROVE FOR TEMP POWER. USE APPROVED JUNCTION BOX AT OLD SERVICE AREA. CALL FOR FINAL ONCE ALL IS COMPLETE |