Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/13/2003 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) INSTALL A SEALING LOCKNUT AT 3/4" E.M.T. CONNECTION AT SERVICE PANEL. 2) I.D. GROUNDING CONDUCTOR AT BOND BUSHIN EITHER GREEN OR BARE COPPER. 3) NEED NEUTRAL FOR EACH A & B PHASE CIRCUIT (8 CIRCUITS NEED 4 NEUTRALS) OR REMOVE 2 CIRCUITS AT OLD SERVICE LOCATION.. 4) PROTECT EXSISTING #14 WIRE AT 15 AMPS MAXIUM CIRCUIT BREAKER. 5) USE PROPER BREAKER AT NEW SERVICE PANEL PER LISTING. |
| 09/19/2003 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) RISER NEEDS TWO CLAMPS BELOW ROOF 1/4". 2) ROOF JACK ON RISER. 3) KICKER BRACE ON RISER ABOVE ROOF IF RISER OVER 3'. 4) IDENTIFY NEUTRALS. 5) NEED WATER AND GAS BONDS. 6) PERMANENT ADDRESS ON SERVICE. 7) 200 AMP SERVICE REQUIRES A #4 GROUND WIRE. 8) BRANCH CIRCUITS REQUIRE NEUTRALS. 9) STRAP 3/4" EMT AT SERVICE AND TOP ENTRY REQUIRES HUB OR SEAL LOCK NUT. |