Permit: T03EL01351
Permit Details
Apply Date:
07/10/2003
Applicant:
BREEZE WAYS INC*C
Description:
UPGRADE:ELECTRIC 200AMP (REPLACE) (APA)
Contractors:
- BREEZE WAYS INC*C
Outstanding Activity Conditions
Permit Number - T03EL01351
Permit Status: Withdrwn
Permit Description: UPGRADE:ELECTRIC 200AMP (REPLACE) (APA)
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 07/10/2003 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Withdrwn
Permit Number: T03EL01351
Permite Description: UPGRADE:ELECTRIC 200AMP (REPLACE) (APA)
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2003 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0245*/ 1) NEW 200 AMP METER BASE FEED AN EXISTING INDOOR RATED DISCONNECT SWITCH. 2) GUTTER MUST BE RATED FOR OUTDOOR USE. 3) GROUNDING ELECTRODE CONDUCTOR SPLICES MUST BE PERMANANT TYPE PER ART 250 NEC. 4) LOAD CENTER TO RIGHT OF DISCONNECT MUST BE OUTDOOR RATED. CAN SEE DAYLIGHT AT TOP FROM INSIDE. 5) EXPOSED WIRING OUTSIDE. 6) THIS SERVICE AND ASSOCIATED WIRING, EQUIPMENT MUST BE BROUGHT UP TO CODE PRIOR TO POWER RELEASE. UNSAFE AS IS. 7) WORK TO BE DONE BY L-11 LICENSED CONTRACTOR. |